Summer Outage
What size generator for window AC and refrigerator?
Use the default WattSizer rule: add running watts, then model the largest startup load while the other selected loads are already running.
The peak-starting assumption is driven by 10,000 BTU window AC. With the default 20% buffer, WattSizer rounds up to the next 100 watts.
| Appliance | Running | Starting | Source note |
|---|---|---|---|
| 10,000 BTU window AC | 1,100 W | 2,800 W | Room AC nameplates vary by efficiency and compressor type; default is a planning value for larger 115 V units. |
| Refrigerator | 180 W | 1,200 W | DOE appliance-use guidance says sample wattages vary by age and features; default is a conservative planning value for a modern full-size refrigerator. |
| Ten LED lights | 100 W | 100 W | LED bulb wattage is printed on each bulb; default assumes ten mixed fixtures at about 10 watts each. |
Try the load yourself
Edit this scenario
| Load | Running watts | Starting watts |
|---|---|---|
Power station estimate
For battery units, the selected running load needs about 0 Wh for 8 hours or 0 Wh for 12 hours before weather, battery age, and inverter losses.
Safety check
Never operate a fuel-burning generator indoors, in a garage, on a porch, or near open windows. Use a listed transfer switch or interlock installed by a qualified electrician for home wiring, and verify actual device nameplates before buying equipment.
Generator or power station?
Fuel generators are useful for motor loads and longer outages, while battery power stations are better for indoor-safe electronics and medical-device planning. For battery sizing, this selected running load is about 13,250 Wh for 8 hours with the same buffer.
Never operate a fuel-burning generator indoors, in a garage, on a porch, or near open windows. Use a listed transfer switch or interlock installed by a qualified electrician for home wiring, and verify actual device nameplates before buying equipment.